EX9033P - RS485 3 RTD input with individual channel configuration
EX9033P Analog In 16 bit RS485 Out I/O device. 3 RTD In channels with individual config. e.g. PT100, PT1000. Break-line detection and wide temperature range
Descrizione
The EX9033P Analog In 16 bit module for RTD excels at use for temperature measurement with a resistance temperature detector. The Analog In 16 bit module has 10 Hz sampling rate as well as a built-in open-loop detection. Each channel of the Analog In RS485 module can be configured seperately and the module may be operated in a wide temperature range.
Features:
- 3 input channels
- support all popular resistive thermometer
- individual channel configuration
- break-line detection
- output as RS485-interface
- in- and output galvanically isolated
- manual configuration or with supplied software
- power supply 10 - 30VDC
Supported thermometers:
- Pt100 a=0.00385
- Pt100 a=0.003916
- Pt1000 a=0.00385
- Cu100 a=0.00421
- Cu100 a=0.00427
- Cu1000 a=0.00421
- Ni120
Caratteristiche
Interfaccia |
|
---|---|
Connessione | RS485 |
Velocità | 300 - 115200 bps |
Connettore | Terminal Block |
Protocollo | ASCII |
Ingresso / Uscita |
|
Tipo | RTD |
Canali in | 3 |
Isolamento | Yes |
Analog-In |
|
Canali | 3 differential |
Risoluzione | 16 bit |
Frequenza di campionamento totale | 15.7 Hz |
Precisione | ± 0.1 % |
Deriva zero | ± 0.5 µV/°C |
Span Drift (Span Drift) | ± 20 ppm/°C |
Tipo di sensore | PT100, PT1000, CU100, CU1000, NI120 |
Ingresso sensore | 3 x 2/3/4 wire |
Caratteristiche |
|
Tensione di isolamento | 3000 V |
Extra | Individual channel configuration, Break line detection |
Sistema |
|
Potenza max. | 1 W |
Ingresso di alimentazione | 10~30V DC |
Involucro |
|
Continua | Din Rail Mounting |
Dimensione | 100 x 70 x 25mm |
Peso | 110g |
Ambiente |
|
Temperatura | -25~75°C |
Temperatura di conservazione | -30~75°C |
Certificazione | CE / FCC / WEEE / RoHS |
Altro |
|
incluso nella consegna | Din Rail Mounting Kit |